Technology functions
CPU 317T: Technology Functions
6-220 A5E00251798-03
Note
To change several parameters which do not require a restart and come into effect
immediately in one pass, group all parameter deltas, and then enable these.
Procedure:
1. Use MC_WriteParameter to set the technology parameter
activationmodechangedconfigdata (ParameterNumber = 4001) to
COLLECT_CHANGED_CONFIG_DATA (82).
This forms a collection of all subsequent changes at the relevant technology
object.
2. Use MC_WriteParameter to change the relevant technology parameters.
3. Set ACTIVATE_CHANGED_CONFIG_DATA (81) at MC_WriteParameter
activationmodechangedconfigdata to apply all changes.
This procedure is called for when editing technology parameters requiring identical
values in all data records.