Technology functions
CPU 317T: Technology Functions
A5E00251798-03
6-235
ErrorID
Error message Description / to correct or avoid error
8089 Invalid data length (ANY pointer) Specified data length is invalid. Possible causes are:
The length exceeds 64 bytes
The specified length plus the start address defines an
address outside of the I/O image DP(DRIVE).
808C Pointer format is invalid or not
supported
The ANY pointer contains illegal specifications. Accepted
areas:
I, O, M, DB, DI
Accepted data types:
BYTE, CHAR, WORD, INT, DWORD, DINT, REAL
808D Data record length out of range An attempt was made to transfer a data record with a
length of more than 240 bytes. Reduce the length
definition in the ANY pointer.